Description
Blue Star Cassette AC 2 Ton Inverter ID324MBTUR1
2.02 TR is Single Phase model
Product Information Product Code ID324MBTUR1
Product Series MB
Performance Parameters Nominal Cooling Capacity (TR) 2.02 TR
Air Conditioner Type Inverter Cassette
Star Rating – As Per BEE 3-Star
(Rated) Voltage/Frequency/Phase 230 V/50 Hz/1 Ph
Cooling Capacity (Min~Max) (Watt) 7100 (2627~7105)
Cooling Capacity (Min~Max) (BTU/Hr) 24225 (8970~24244)
Rated Cooling Capacity (50% Load) (Watt) 3550
Cooling Rated Power Input (Min~Max) (Watt) 2150 (676~2201)
Cooling Power Input (50% Load) (Watt) 915
ISEER 3.86
Electricity Consumed in 1600 Hours. (Units/Year) 1425.03
Nominal Current (Cooling in Amps)/Running Current 9.22
Air Flow Volume (Wet CFM) (High/Medium/Low) 700/556/481
Compressor, Refrigerant & Ambi- ent Operations Noise Level Indoor (High/Medium/Low) In dB(A) 50.8/45.3/41.6
Moisture Removal (Litres/Hour) 2.9
Compressor Type Inverter Rotary
Compressor Warranty 5 Years
Eco-Friendly Refrigerant R-32
Ambient Temp Range (Cooling)°C Up to 52ºc
User Interface – Remote Remote LCD Remote
Product Dimensions, Weight & Input Power Supply IDU Net Dimension (W X H X D) mm 840 x 205 x 840
IDU Grill Net Dimension (W X H X D) mm 1020 x 50 x 1020
Input Power Supply INDOOR UNIT
Net Weight IDU 22.7 Kg
Net Weight IDU Grill 5.8 Kg
ODU Net Dimension (W X H X D) mm 890 x 673 x 342
Net Weight ODU 39 Kg
Gross Weight ODU 42.3 Kg
Noise Level Outdoor In dB(A) 57
Power Supply to ODU Source(Core/Gauge) sqmm 3C * 2.5
Power Supply to IDU Source(Core/Gauge) sqmm 4C * 2.5
Tube Size & Piping Capability Cable from ODU to IDU (Communication Cable) sqmm Included in ODU to IDU wire
Suction Tube Size Outer Diameter Inch (mm) 5/8″(15.88mm)
Liquid Tube Size Outer Diameter Inch (mm) 3/8” (9.52mm)
Max Piping Capability Total (metre) 30
Max Piping Capability Vertical (metre) 15
Refrigerant Additional Charge Beyond 5M (g/m) 24
Reviews
There are no reviews yet.